Let’s begin with water vapour. You can’t see it, you can’t smell it, but it’s always present. The warmer the air, the more water vapour it can hold (see table). Usually, the air contains less than the maximum possible amount of vapour — this is expressed as Relative Humidity (RH).
Example calculation: If the RH of air is 50% at 15°C, then the air contains 50% × 13 g = 6.5 g of water vapour per cubic metre (g/m³).
When warm air cools, it can hold less vapour. Once RH rises to 100%, the excess vapour turns into tiny droplets (condensate). The temperature at which the cooling air starts forming droplets is called the dew point — think of dew on the grass. The dew point is expressed in °C.
Even when air has not yet condensed, it still has a dew point. This dew point is always lower than the current temperature of the air. In the above example, 15°C air containing 6.5 g moisture will only start condensing once it cools below 3°C (see Table 1). Thus, the dew point is 3°C.
As long as the ambient temperature of the compressed air system remains above the dew point, no condensate will form inside. The lower the dew point, the drier the air.
Compressed air is at a much higher pressure than ambient air, which changes its behaviour. In this case, we speak of a pressure dew point. The principle remains the same: condensate will form once the temperature falls below the dew point.
Producing compressed air requires around 7–9 m³ of ambient air for every 1 m³ of compressed air (at 7–9 bar). This means that the same multiple of vapour and dirt particles is concentrated into that single cubic metre. However, the air at 15°C can only hold 13 g/m³. The surplus water vapour will condense already inside the compressor.
Example calculation: If RH = 50% at 15°C, then 6.5 g/m³ vapour is present. Compressed to 8 bar: 6.5 g × 8 = 52 g/m³ → 52 – 13 g/m³ = 39 g/m³ will condense. The compressed air is now fully saturated: RH = 100% at 15°C.
In practice, compression generates heat. Up to 85% of the electricity consumed by a compressor turns into heat, raising air temperature to 70–90°C. Hotter air can hold more vapour (see table). After compression, RH will almost always be 100%, and each m³ may contain up to 290 g vapour.
If this “wet” compressed air is not dried, it will inevitably cause condensation in your system as it cools back down to ambient temperature.
Condensate always forms at the coldest spot in the system, which is often not the compressor room.
To prevent these issues, the dew point of compressed air must always be lower than the coldest temperature the milking parlour (or environment) will reach.
There are three main types of compressed air dryers:
We recommend fitting every dryer with a test connection for quick and easy dew point measurement.