Skip to main content
With this data you can compare valves with each other

With this data you can compare valves with each other

To assess the flow capacity (output) of a valve, objective comparison values are required. The flow of a valve depends on several factors, such as:

  • Flow cross-sectional area
  • Absolute inlet pressure
  • Absolute outlet pressure
  • Pressure drop across the valve
  • Temperature
  • Medium
  • Relative ratios

For proper comparison or calculation, all values must be specified in the same way. For this purpose, the unit normal litre is used: Nl or Ndm³. This represents one litre of air at 0 °C at atmospheric (ambient) pressure.

kv value

The measurement is performed with water and indicates the number of litres of water per minute flowing through the valve at a pressure drop of 1 bar.

Unit: Ndm³/min

  • kv × 0.07 = Cv
  • kv × 1.259 = S
  • kv × 68.65 = Qn
  • kv × 0.06 = Kv

Kv value

As above, but expressed in SI units: Nm³/h.

  • Kv × 16.67 = kv

Cv factor

The measurement is performed with water and indicates the number of US gallons per minute at a temperature of 15.6 °C (60 °F) and a pressure drop of 0.07 bar (1 PSI).

Notation: US gallons/min.

  • Cv × 981.5 = Qn
  • Cv × 0.829 = f
  • Cv × 14.3 = kv
  • Cv × 8.18 = S

f factor

Equivalent to the Cv factor but expressed in imperial US gallons/min.

  • f × 1.206 = Cv

S equivalent diameter

Here, the valve (resistance, output) is compared with a measuring orifice of equal flow capacity.

Unit: mm²

  • S × 54.53 = Qn
  • S × 0.055 = Cv
  • S × 0.794 = kv

Qn normal flow capacity

This indicates the output of a valve at a supply pressure of 6 bar and a pressure drop of 1 bar. Since the boundary conditions are not always clearly defined, the comparison is not always entirely precise.

Unit: Nl/min

  • Qn × 0.001 = Cv
  • Qn × 0.015 = kv
  • Qn × 0.018 = S

Contact

Specialist of pneumatics

Ad van Gemert